This is a quadruplex 600V URD cable with four 2 AWG aluminum conductors. It is designed for secondary power distribution circuits and can be installed by direct burial or in duct. It works in wet and dry locations, and the maximum operating temperature is 90°C.
The conductors are concentric-strand or compressed 1350-H19 series aluminum. They are cabled together, with surface printing for identification, and the neutral conductor has a yellow stripe. The insulation is black cross-linked polyethylene (XLP). It is water tight and resists corrosive substances, oil, heat and flame.
The cable can also be supplied pre-pulled into duct as an option.
- Voltage
- 600 V
- Conductor
- 1350-H19 series aluminum, concentric strand or compressed
- Conductor size
- 2 AWG, 7 strands
- Neutral size
- 2 AWG, with yellow stripe
- Insulation
- Black cross-linked polyethylene (XLP)
- Insulation thickness
- 60 mils
- Single-phase conductor
- 0.403 in
- Outer diameter
- 0.973 in
- Weight
- 375 lbs per 1000 ft
- Ampacity, direct burial
- 155 A
- Ampacity, in duct
- 115 A
- Max temperature
- 90°C, wet and dry locations
- Installation
- Direct burial or in duct