This is 6/3 NM-B non-metallic sheathed cable, sold as a 15-foot cut. It is used in normally dry residential installations as branch-circuit wiring for outlets, switches, lighting and other loads. It may be fished through masonry or tile walls where it is not exposed or subject to excessive moisture or dampness.
Each conductor is insulated with color-coded PVC and a nylon covering that meets the thickness required for Type THHN. The ground is soft, bare copper. A 30 mil color-coded PVC sheath rated 90°C covers the finished assembly. The cable is lead free and RoHS compliant.
The cable is rated at 600 volts. The conductor insulation is rated at 90°C dry, but ampacity is limited to 60°C under the 2008 and 2011 NEC. Its applications are outlined in Article 334 of those editions.
- Type
- NM-B non-metallic sheathed cable
- Length
- 15 feet (cut length)
- Conductor size
- 6 AWG
- Conductors
- 3
- Ground wire
- 10 AWG, soft bare copper
- Voltage rating
- 600 volts
- Ampacity
- 55 amps allowable
- Temperature rating
- 90°C conductor insulation; ampacity limited to 60°C
- Insulation
- Color-coded PVC with nylon covering, Type THHN thickness
- PVC thickness
- 0.76 mm / 0.029 in
- Nylon thickness
- 0.13 mm / 0.005 in
- Sheath
- 30 mil color-coded PVC, rated 90°C
- Cable dimensions
- 16.0 mm / 0.62 in nominal
- Weight
- 0.357 lbs per foot
- Standards
- UL 83, UL 719, Federal Specification A-A-59544, NEC requirements
- Compliance
- Lead free, RoHS compliant
- Use
- Indoor residential, dry locations