This is aluminum quadruplex URD (underground residential distribution) wire with a 2-2-2-4 configuration. It has three size 2 AWG aluminum conductors and a size 4 AWG neutral. It is rated 600 V and made for direct burial.
The insulation is water tight, so the wire can be used in wet and dry places. It resists heat, flame and corrosive substances, with a maximum operating temperature of 90°C. It is used for secondary distribution circuits for power and for outdoor applications.
- Type
- Dyke quadruplex aluminum conductor, underground direct burial, 600 V URD
- Material
- Aluminum conductor
- Conductor size
- 2 AWG
- Neutral size
- 4 AWG
- Stranding
- 7
- Single-phase conductor
- 0.403 in
- Insulation thickness
- 60 mils
- Outer diameter
- 0.973 in
- Weight
- 367 lbs per 1,000 ft
- Ampacity (direct burial)
- 155 Amps
- Ampacity (in-duct)
- 115 Amps
- Max temperature
- 90°C
- Installation
- Underground, direct burial
- Resistance
- Water tight, heat, flame and corrosive substances
- Standards
- RUS accepted; ASTM B-230, B-231, B-609, B-901